Does conduit fill include insulation thickness or just copper?

Conduit fill uses total conductor cross-sectional area including insulation, not bare copper area alone. NEC Chapter 9 Table 5 values already represent insulated conductor area, while bare equipment grounds are taken from Table 8. That is why two conductors with the same copper gauge but different insulation types can produce different fill results.