    How much whole-house ventilation does ASHRAE 62.2 require for a 2000 sq ft, 3-bedroom house?

    Using the ASHRAE 62.2-2019 formula Qtot = 0.03 x Afloor + 7.5 x (Nbr + 1), a 2000 sq ft, 3-bedroom home needs 0.03 x 2000 = 60 CFM from floor area plus 7.5 x 4 = 30 CFM from occupants, for 90 CFM of continuous airflow. That is the continuous whole-house rate before any local exhaust is added.