    Standard pipe slope requirements chart

    Under the IPC, horizontal drains 2-1/2 inches and smaller need 1/4 inch per foot (2%), 3-inch through 6-inch pipe may use 1/8 inch per foot (1%), and 8-inch and larger may use 1/16 inch per foot — all provided the design keeps at least a 2 ft/s scouring velocity. The UPC is generally stricter, so check your adopted code and AHJ; the calculator applies the correct minimum for your pipe size.

    Run the numbers for your project

    Use the Drain Slope Calculator (1/4 per Foot) to get an exact answer for your inputs.

    Open the calculator

    Related questions

    Estimates and general guidance only. Verify against your local code and AHJ before any installation. Gas, electrical, and refrigerant work is hazardous to untrained users.