    NEC Motor Circuit Sizing Calculator (Article 430)

    What size breaker and wire do I need for a 10 hp 460V three-phase motor?

    Select three-phase AC, 460 V, and 10 hp; the calculator uses the FLC from NEC Table 430.250 rather than the nameplate, per 430.6(A)(1). Conductors are sized at a minimum 125% of FLC (430.22), the short-circuit/ground-fault OCPD is capped by Table 430.52 (for example 250% of FLC for an inverse-time breaker), and the disconnect is at least 115% of FLC (430.110). The tool rounds the OCPD up to the next standard size.

    Run the numbers for your project

    Use the NEC Motor Circuit Sizing Calculator (Article 430) to get an exact answer for your inputs.

    Open the calculator