Skip to main content

    Ampacity with derating

    Apply ambient-temperature correction (310.15(B)) and the more-than-three-conductor adjustment (310.15(C)(1)) to a base ampacity, then cap it at the termination temperature (110.14(C)). All three candidate values are shown so you can see which one binds.

    02Conductor
    Life-safety calculation

    Electrical systems sized incorrectly can cause fire, explosion, electrocution, or carbon monoxide poisoning. Results are estimates only and must be reviewed by a licensed professional before any work is performed. Do not install based on these results alone. Read full terms.

    Frequently Asked Questions

    What wire size do I need for a 50-amp circuit?

    For a continuous 50-amp load on copper THHN at 75°C terminations, NEC Table 310.16 calls for #6 AWG (65A allowable ampacity after 125% sizing). Use #4 AWG aluminum for the same load. Always derate for ambient temperature above 30°C and for more than three current-carrying conductors in a raceway.

    Does NEC require 75°C or 90°C ampacity?

    Conductors can be rated 90°C, but terminations on most devices are listed for 75°C — so you size from the 75°C column unless the equipment is specifically listed for 90°C terminations. Use 90°C ampacity only as the starting point for derating calculations.

    How do I derate wire for high ambient temperature?

    NEC Table 310.15(B)(1) gives an ambient temperature correction factor — multiply the 90°C ampacity by the factor for your installation temperature, then verify the corrected value still exceeds 125% of the continuous load.