Cable Attenuation Calculator (dB)

Estimate twisted-pair insertion loss (attenuation) for a structured-cabling run and check it against the ANSI/TIA-568.2-D 100 m channel limit.

  1. Pick the cable category Choose Cable category — Cat 5e (100 MHz), Cat 6 (250 MHz), or Cat 6A (500 MHz) — which sets the worst-case attenuation table used.
  2. Enter the run length Type the Run length in meters; insertion loss scales linearly as dB/100 m × length / 100.
  3. Select the test frequency Set Frequency to one of the tabulated TIA reference frequencies for that category (e.g. 1, 10, 100, 250, or 500 MHz).
  4. Calculate and check the channel Press Calculate to read the insertion loss in dB and whether the length stays within the 100 m channel maximum.

How far can I run Cat 6 cable?

ANSI/TIA-568.2-D limits a balanced twisted-pair channel to 100 m, made up of a 90 m permanent link plus up to 10 m of patch and equipment cords. The calculator flags any run length over 100 m as exceeding the channel limit regardless of category. Cat 6, Cat 6A, and Cat 5e all share this same 100 m channel maximum.

What is insertion loss on a network cable?

Insertion loss is the signal attenuation across the run, expressed in decibels. This tool multiplies the TIA-568.2-D worst-case component limit (dB per 100 m at the selected frequency) by length / 100. These are planning limits — a real installed run measures lower, so always field-certify with a cable analyzer.

Why are only certain frequencies available?

The calculator uses the standard TIA-568.2-D reference frequencies where horizontal-cable insertion-loss limits are tabulated, such as 1, 10, and 100 MHz for Cat 5e and up to 250 or 500 MHz for Cat 6 and Cat 6A. Each category only offers frequencies within its rated bandwidth, so you cannot enter an arbitrary value.