Skip to main content

    Voltage drop

    Estimate conductor voltage drop with the approximate K-method (Table 8) or the exact R/X method (Table 9), then check it against the NEC's recommended 3% branch / 3% feeder / 5% combined guidance.

    02Parameters
    Life-safety calculation

    Electrical systems sized incorrectly can cause fire, explosion, electrocution, or carbon monoxide poisoning. Results are estimates only and must be reviewed by a licensed professional before any work is performed. Do not install based on these results alone. Read full terms.

    Frequently Asked Questions

    What is the maximum voltage drop NEC allows?

    NEC 210.19(A) and 215.2(A) informational notes recommend a maximum 3% voltage drop on branch circuits and 5% combined on feeder + branch — they are recommendations, not mandates, but most AHJs enforce them.

    How do I calculate voltage drop for a long run?

    Use Vd = 2 × K × I × D / CM for single-phase (×√3 for three-phase), where K is conductor resistivity (12.9 copper / 21.2 aluminum), I is load current in amps, D is one-way distance in feet, and CM is conductor circular mils. Increase wire size whenever the result exceeds 3% on a branch circuit.

    Does voltage drop require upsizing the EGC?

    Yes — NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally when the ungrounded conductors are upsized for voltage drop, so the EGC maintains its fault-clearing capacity.