Install GFCI and AFCI Receptacles
Scope
Install or replace GFCI and AFCI receptacles. Covers the NEC 2023 coverage table (where each is required), the LINE / LOAD wiring convention, multi-device protection from a single GFCI, and what to do when the test button doesn't work.
Safety
Receptacle replacement is the lowest-risk in-residence electrical work, but the failure mode is still the same: a believed-off conductor that is actually energized. NFPA 70E §120.5 verification before any wire is touched. UL 943 self-test GFCIs introduced ~2015 have a miswire-lockout — wires landed on the wrong terminals make the device dead on arrival.
Pre-Check
9 items · complete before you startSteps
Pre-identify LINE vs LOAD (with breaker ON)
- With breaker ON, use a non-contact voltage tester at each cable in the box
- The conductor pair (black + white) reading LIVE is the LINE side (incoming feed)
- Any other cable reading dead until a downstream device is turned on is the LOAD side
- Mark the LINE cable with tape so you remember after de-energization
- Skip this step if the box has only ONE cable — the GFCI protects only its own face, no downstream protection.
Establish electrically safe condition
- Turn off the breaker for this circuit
- Lock and tag the breaker
- Test your non-contact tester on a known-live source
- Verify zero energy at the receptacle box
- Re-test the tester on the known-live source
Remove the old receptacle
- Unscrew the receptacle from the box and pull it forward
- Photograph the wiring BEFORE disconnection
- Note which wires were backstabbed (push-in) vs side-screw — you'll re-land on side screws
- Disconnect each wire — keep the original LINE side identified
Wire the new GFCI / AFCI receptacle
- LINE side (incoming): black to brass screw, white to silver screw — both marked LINE
- LOAD side (to downstream protected devices): black to brass LOAD screw, white to silver LOAD screw
- GROUND (bare or green) to green screw on the device
- Pigtail ground to the box if the box is metal
- Wrap the device's screw terminals with electrical tape if the box is metal and crowded — prevents accidental contact with the box
- Torque terminal screws to the device label spec — usually 12–20 in-lb
- Modern UL 943 GFCIs miswire-lockout if LINE and LOAD are reversed. The reset button will not click in. If this happens, de-energize and swap the connections.
- On an AFCI breaker installation (panel-side), the white pigtail from the AFCI breaker lands on the NEUTRAL bus AND the branch-circuit white lands on the breaker's neutral terminal — NOT directly on the neutral bus.
Mount, restore, and test
- Fold the receptacle into the box and secure with the 6/32 screws
- Install the cover plate
- Restore the breaker
- Press TEST — the reset button should pop out and the receptacle should de-energize
- Press RESET — the button should click in and power return
- Plug in a load on the protected receptacle AND any downstream receptacle to confirm coverage
- Mark "GFCI Protected" stickers on any downstream receptacles fed from the LOAD terminals
- NEC §406.4(D)(3) — replacement receptacles in spaces requiring GFCI must be GFCI-protected.
- NEC §210.8(F) — GFCI required on outdoor outlets and most dwelling-unit outdoor branch circuits.