Skip to main content
    All guides
    ElectricalIntermediate

    Bond Metallic Water & Gas Piping (NEC §250.104)

    Time
    45–90 min
    Steps
    7
    Pre-check
    9 items
    Skill
    Intermediate

    Scope

    Bond metallic water piping and gas piping to the electrical grounding system per NEC §250.104. Frequently missed during plumbing work that replaces a section of metal pipe with plastic — the plastic section breaks the bond and energizes the downstream metal under a fault. This is the electrical guide most relevant to the plumbing audience.

    Safety

    Read before starting

    Lower-energy than panel work, but the work happens at the service equipment — the line side is utility-fed and stays energized. NFPA 70E §120.5 verification before any work at the panel. If the bond is missing or broken, accessible metal piping can become energized under a single-fault condition.

    Pre-Check

    9 items · complete before you start
    0 / 41 complete

    Steps

    01

    Inspect the existing service-entrance bond

    • Open the main service panel cover (see Establish electrically safe condition step below)
    • Look for an existing bonding conductor from the panel ground bus to the incoming metal water service — usually #6 bare copper
    • The clamp lands within 5 ft of the water-service entrance to the building (NEC §250.52(A)(1))
    • If you find no bond — that is the #1 finding to fix
    • Photograph the existing bond from panel to first clamp for your records
    Code notes
    • NEC §250.104(A) — interior metal water piping must be bonded to: the service equipment, the grounded conductor, the grounding electrode conductor, OR the grounding electrode itself.
    • NEC §250.52(A)(1) — metal underground water pipe ≥10 ft contact qualifies as a grounding electrode; must be supplemented by another electrode.
    02

    Establish electrically safe condition at the panel

    • Turn off the MAIN breaker
    • Lock and tag the main
    • Test your non-contact tester on a known-live source elsewhere
    • Verify zero energy at the bus bars (line side stays hot)
    • Re-test the tester on the known-live source
    ⚠ Warnings
    • Bonding conductor work at the panel exposes you to the bus bars — stay below the main breaker.
    Continue Gate:Have you (1) turned off the breaker, (2) tested your non-contact tester on a KNOWN-LIVE source, (3) verified zero energy at the conductors you are about to touch, and (4) re-tested the tester on the known-live source to confirm it still works? (NFPA 70E §120.5)
    03

    Install the water-pipe bond (if missing)

    • Land a #6 bare copper conductor on the panel's ground bus
    • Route to the incoming water service pipe (the cold water entrance)
    • Attach with a listed ground clamp within 5 ft of the building entrance
    • Clean the pipe surface bright with emery cloth before clamping — corrosion = high resistance = bad bond
    • For a PVC water service entering and converting to copper inside: the bond goes on the INTERIOR copper, not the buried PVC
    Water & Gas Piping Bonding· NEC Wiring
    Code notes
    • NEC §250.104(A)(1) — bonding jumper sized per Table 250.66.
    • NEC §250.68(C)(1) — interior metal water piping ≤5 ft from entry can be a connection point for the grounding electrode conductor.
    04

    Bond around any plastic break

    • Identify each plastic section in an otherwise-metal system
    • Install a #6 jumper across the plastic — landed on listed ground clamps on the metal pipe upstream AND downstream
    • Clean both pipe surfaces bright before clamping
    • A common plastic break: PEX repair in a copper run. The downstream copper becomes electrically isolated from the bonded portion.
    • Another common break: dielectric unions at the water heater. The hot-side copper is isolated from the cold-side copper. Bond across with a jumper.
    Tips
    • A dedicated water-heater "dielectric union jumper" is sold pre-made — short #6 copper with two clamps.
    05

    Bond metallic gas piping per NEC §250.104(B)

    • CSST (the yellow flexible gas line) requires bonding to the electrical system at the point of entry to the building, with a #6 copper jumper to a CSST manufacturer-supplied clamp
    • Rigid black-iron gas piping is bonded by the equipment grounding conductor of the appliance it serves (per §250.104(B) and §250.104(A)(2)) — verify the appliance EGC is intact
    • Some AHJs require an explicit gas-piping bond even for rigid black iron — confirm locally
    • Bond goes back to the panel ground bus OR to the grounding electrode system
    ⚠ Warnings
    • Unbonded CSST has been linked to fire after nearby lightning strikes — the EGC bond is a safety-critical install requirement.
    Code notes
    • NEC §250.104(B) — metal gas piping that's likely to become energized must be bonded to the service equipment.
    • CSST manufacturer instructions (TracPipe, Gastite, etc.) specify the bonding clamp and jumper sizing — follow them, the listing depends on it.
    06

    Verify continuity and restore power

    • Visually inspect every new clamp — pipe bright, screw torqued
    • With panel still de-energized: use a multimeter on continuity (Ω) to verify <1 Ω between panel ground bus and every bonded pipe segment
    • Reinstall the deadfront
    • Restore the main breaker
    • Verify no faults — no breakers tripping, no abnormal smells
    07

    Document for the plumbing audience

    • After plumbing work that adds a plastic section to a metal system: ALWAYS bond across the break before closing the wall
    • Photo of every bond clamp goes in the home records — the AHJ inspector can't see them after drywall
    • Note the pipe material change in the plumbing as-built so future trades know