electrical troubleshooting
GFCI won't reset
Common symptoms: gfci won't reset; gfci tripped; gfci dead; outlet not working; gfci button won't stay in
Stop and call a pro if:
- lockout-tagout-required
Step-by-step diagnostic flow
Step 1
Before opening the GFCI device, establish an electrically safe work condition.
Step 2
With the breaker ON and the GFCI in place, do you have line-side voltage at the device? (You can confirm without opening it by checking the upstream breaker is on and not tripped.)
Step 3
Unplug everything downstream of this GFCI (including any other receptacles it protects) and try to reset.
GFCIs protect themselves AND any downstream outlets wired to LOAD. A fault on a downstream device looks identical to one at the GFCI itself.
Step 4
How old is the GFCI device? (Estimate is fine.)
UL 943 has required self-test and end-of-life lockout since ~2015. A modern GFCI that won't reset is most commonly at end of life.
Step 5
If this device was recently installed, check that the supply (incoming hot/neutral) is on the LINE terminals, not LOAD. Modern GFCIs miswire-lockout if reversed.
Possible outcomes
Stop — establish electrically safe condition first
high confidenceNFPA 70E §120.5 — verify zero energy before opening the device.
- Turn off the breaker and verify with a known-good tester before pulling the GFCI
Upstream breaker is tripped
high confidenceThe GFCI cannot reset without line-side power.
- Reset the upstream breaker
- If the breaker won't reset either, see 'Breaker keeps tripping' workflow
Likely a ground fault on a downstream device
high confidenceThe GFCI resets with downstream loads disconnected, so the fault is on something it protects.
- Plug devices back in one at a time until the GFCI trips again — the last device added is the source
- Replace or repair that device
- Which device caused the trip
- Whether it's wet, damaged, or older
GFCI is likely at end of life — replace the device
high confidenceUL 943 self-test GFCIs enter an auto-monitoring lockout when the sensing circuit fails — refusing to reset even on a known-good circuit. Service life is typically 10–15 years.
- With the breaker off and verified de-energized, replace the GFCI with a current UL 943 self-test device
- Match LINE/LOAD terminals to the wires you removed
- GFCI brand and date code if visible
- Whether other GFCIs in the home are the same vintage (likely all near end of life)
Likely miswire — LINE and LOAD terminals reversed at installation
high confidenceModern GFCIs miswire-lockout if supply is landed on LOAD instead of LINE.
- De-energize and verify zero energy
- Identify the incoming supply cable (use a non-contact tester with breaker on, then de-energize again before working)
- Land supply on LINE; downstream devices on LOAD
- Photos of existing wiring before re-landing
Pro launch updates
Get notified when Pro launches, plus a monthly code-change digest. Email only — no account required.