Do I have to upsize wire for a long run?
Ampacity tables do not care about distance, so you size conductors for ampacity first. But voltage drop is a separate check (NEC informational notes recommend 3% on branch circuits and 5% total), and on runs longer than about 75–100 ft you often need to bump up one wire size to keep voltage drop in range. Use the voltage-drop calculator alongside ampacity sizing to confirm.
Run the numbers for your project
Use the NEC Wire Size & Ampacity Calculator (310.16) to get an exact answer for your inputs.
Open the calculatorRelated questions