    What wire size do I need for a 50-amp circuit?

    For a continuous 50-amp load on copper THHN at 75°C terminations, NEC Table 310.16 calls for #6 AWG (65A allowable ampacity after 125% sizing). Use #4 AWG aluminum for the same load. Always derate for ambient temperature above 30°C and for more than three current-carrying conductors in a raceway.

    Run the numbers for your project

    Use the NEC Wire Size & Ampacity Calculator (310.16) to get an exact answer for your inputs.

    Open the calculator

    Related questions

    Estimates and general guidance only. Verify against your local code and AHJ before any installation. Gas, electrical, and refrigerant work is hazardous to untrained users.