hvac troubleshooting
Heat pump not heating in cold weather
Common symptoms: heat pump cold air; heat pump not heating; heat pump weak heat; cold weather no heat
Stop and call a pro if:
- burning odor
- smoke
- sparks
- frozen outdoor unit
Step-by-step diagnostic flow
Step 1
Any burning smell, smoke, or sparks from the indoor or outdoor unit?
Step 2
Is the outdoor unit currently covered in frost or ice, with the fan off and steam rising? This is a normal defrost cycle (typically 5–15 minutes).
Defrost cycles run periodically in cold weather. The reversing valve sends hot refrigerant to the outdoor coil to melt frost — air handler may blow cool air temporarily.
Step 3
What is the current outdoor temperature?
Step 4
Is the thermostat showing 'AUX' or 'Emergency Heat' on?
Below the heat-pump balance point (typically 25–35 °F depending on unit and load), auxiliary electric strips or a backup furnace should kick in.
Step 5
Check the indoor air filter and supply registers. Is the filter heavily clogged or are registers blocked?
Possible outcomes
Stop and seek professional help immediately
high confidenceBurning smell, smoke, or sparks indicate active hazard.
Normal defrost cycle — wait and observe
high confidenceDefrost cycles are a designed part of heat-pump operation in cold weather. Cool air from the indoor unit during defrost is expected.
- Wait 5–15 minutes for the cycle to complete
- Verify heat returns when the outdoor fan restarts
- If defrost recurs more often than every 60 minutes or runs >20 minutes, escalate to a pro
- Defrost frequency and duration
- Outdoor temp and humidity
- Equipment make/model
Below balance point — auxiliary heat is running as designed
high confidenceHeat-pump capacity falls with outdoor temperature. Below the balance point, auxiliary heat is supposed to engage.
- Run the balance-point calculator with your AHRI 47/17 °F capacities to confirm expected behavior
- Expect higher utility bills during cold snaps when aux runs
- If aux stays on for days even after weather warms, escalate
- Make/model
- AHRI rated capacities at 47 °F and 17 °F
- Design heating load
Auxiliary heat should be on but isn't — call a pro
medium confidenceBelow 20 °F with no aux indicator suggests a wiring, control-board, or staging issue.
- Document indoor and outdoor temps at multiple times
- Photograph thermostat display
- Do not attempt to wire the aux relay yourself
- Thermostat make/model
- Equipment make/model
- Time-stamped temp readings
Restricted airflow — replace filter and clear registers
high confidenceHeavy filter restriction starves the indoor coil and reduces capacity.
- Replace filter with same MERV rating (do not jump to MERV 13+ without checking blower static pressure)
- Open all supply registers; do not close more than 10% of the system
- Re-test heating after 30 minutes
Heat pump underperforming — professional diagnosis needed
low confidenceOutdoor temp is above the typical balance point, no obvious airflow restriction, and heat is still weak.
- Note supply-air temperature with a probe thermometer (should be 90–105 °F in heat mode for a working HP at 35–47 °F outdoor)
- Capture system make/model and any error codes
- Do not open the outdoor unit
- Supply air temp
- Outdoor temp
- Equipment make/model
- Any error codes
Pro launch updates
Get notified when Pro launches, plus a monthly code-change digest. Email only — no account required.