Does the ground wire count in conduit fill?
Yes. Every conductor in the raceway counts toward fill area, including equipment grounding conductors and the neutral, whether insulated or bare. Use the actual conductor area from Chapter 9 (Table 5 for insulated, Table 8 for bare) — the ground is not exempt, even though it is not a current-carrying conductor for derating purposes.