    What is the maximum conduit fill percentage?

    NEC Chapter 9, Table 1 sets the limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more conductors. The two-wire case is the strictest because of how conductors pack. These percentages keep pulling tension and heat dissipation reasonable; exceed them and you risk damaging insulation during the pull.

    Run the numbers for your project

    Use the NEC Conduit Fill Calculator (Chapter 9) to get an exact answer for your inputs.

    Open the calculator

    Related questions

    Estimates and general guidance only. Verify against your local code and AHJ before any installation. Gas, electrical, and refrigerant work is hazardous to untrained users.