NEC Conduit Fill Calculator (Chapter 9)
What is the maximum conduit fill percentage?
NEC Chapter 9, Table 1 sets the limits: 53% for a single conductor, 31% for exactly two conductors, and 40% for three or more conductors. The two-wire case is the strictest because of how conductors pack. These percentages keep pulling tension and heat dissipation reasonable; exceed them and you risk damaging insulation during the pull.
Run the numbers for your project
Use the NEC Conduit Fill Calculator (Chapter 9) to get an exact answer for your inputs.
Open the calculatorRelated questions
Pro launch updates
Get notified when Pro launches, plus a monthly code-change digest. Email only — no account required.